Part number 550-100-116/0714
95
SlimFit
COMMERCIAL CONDENSING GAS-FIRED WATER BOILER
Boiler Manual
Sola Information and Operations screens (continued)
Press the boiler icon
on the home page to
go to the information
screen.
Use the Operation screen (below) to
r manually activate central heating or DHW.
r manually set the ring rate
r enable/disable the burner
r change normal and time of day setpoints for CH
&IRINGRATEBOX (rate side of screen)  Use to manually set the
blower speed. When the box is pressed, a blower speed screen
opens, and allows:
r numerically entering the ring rate.
r selecting manual or automatic operation of ring rate:
a. Automatic allows the Sola control to set blower speed
(ring rate).
b. Manual in run sets the blower speed to the value set on
the right of the screen during burner run periods.
c. Manual in run and standby sets the blower to the speed
entered on the right side of the screen both during
burner run and standby.
Make sure to return the boiler to automatic opera-
tion aer using the operation screen for manual op-
eration. Failure to do so could cause loss of heating.
e Annunciation screen shows the status of input and interlock
circuits (ON or OFF).
&IGURE Sola display information and operation screen navigation