COMMERCIAL CONDENSING GAS-FIRED WATER BOILER
— Boiler Manual
Install water piping
Use two wrenches when tightening water piping at boiler,
using one of the wrenches to prevent the boiler interior pip-
ing from turning. Failure to support the boiler piping con-
nections to prevent them from turning could cause damage
to boiler components.
General piping information
Additional controls, when required
e Sola module uses temperature sensors to provide both
high limit protection and modulating temperature control,
and is UL353 Limit Controls certied to meet ASME CSD-1
and Section IV requirements. e boiler is equipped with a
manual reset low water cut-o. e Sola module also provides
low water protection by sensing the temperature of the heat
exchanger. Some codes/jurisdictions may require additional
external controls.
Additional limit controls
1. Consult local requirements for other codes/standards to determine if
additional limit devices are needed.
-ULTITEMPERATURE SYSTEMS If the heating system
includes circuits that require lower temperature water (radi-
ant slab circuits, for example) as well as higher temperature
circuits, it is recommended to protect low-temperature
circuits with limit controls that are wired to a Sola external
limit circuit (ILK terminals for manual reset or LCI terminals
for automatic reset).
2. See instructions beginning on page51 for wiring information.
a. e Sola control provides two sets of limit control contacts one
set will cause automatic reset (LCI) and the other will cause manual
reset (ILK) of the Sola control.
b. e Sola control can be reset using the RESET switch on top of
the boiler.
Low water cutoff
1. A push-to-test low water cuto is factory-installed in the boiler. e low
water cuto probe is mounted on the front of the boiler heat exchanger.
2. e low water cuto is manual reset (pushbuon on top of boiler) and
is equipped with a push-to-test switch (top of boiler).
Pressure/temperature gauge
1. Mount the pressure/temperature gauge (shipped loose with the boiler)
in the ¼-inch tapping on top of the boiler supply outlet pipe.
e boiler is shipped with a ¼” NPT pressure and tempera-
ture gauge which has a pressure range up to 75 psig. is
gauge meets ASME requirements up to a relief valve seing
of 50 psig. For higher pressure rated relief valves, a dierent
pressure and temperature gauge with a higher pressure range
is required. When installing a gauge that requires a larger
tapping than the ¼” NPT tapping in the boiler supply mani-
fold, provide an additional tapping in the near boiler piping
BEFORE any isolation valve.
Installing relief valve
$/ ./4 INSTALL A RELIEF VALVEWITH
A PRESSURE HIGHER THAN 03)'
.
is is the maximum allowable relief valve
seing for the SlimFit boiler. e boiler is
shipped with a 30PSIG relief valve. See Re-
placement parts in the back of this manual
for alternate pressure seing relief valves.
4OAVOIDWATERDAMAGEORSCALDING
DUETORELIEFVALVEOPERATIONASPER
local or state codes
:
Discharge line must be connected to re-
lief valve outlet and run to a safe place of
disposal. Terminate the discharge line in
a manner that will prevent possibility of
severe burns or property damage should
the valve discharge.
Discharge line must be as short as possible
and be the same size as the valve discharge
connection throughout its entire length.
Discharge line must pitch downward from
the valve and terminate at least 6” above
the oor drain where any discharge will be
clearly visible.
e discharge line shall terminate plain,
not threaded, with a material serviceable
for temperatures of 375 °F or greater.
Do not pipe the discharge to any place where
freezing could occur.
No shutoff valve shall be installed be-
tween the relief valve and boiler, or in the
discharge line. Do not plug or place any
obstruction in the discharge line.
Test the operation of the valve aer lling
and pressurizing system by liing the lever.
Make sure the valve discharges freely. If the
valve fails to operate correctly, replace it
with a new relief valve.
Failure to comply with the above guidelines
could result in failure of the relief valve
to operate, resulting in the possibility of
severe personal injury, death or substantial
property damage.
Backflow preventer
1. Use backow check valve in cold water supply as required
by local codes.
Install relief valve
1. Install relief valve (shipped loose with the boiler) in the
1¼-inch tapping on top of the boiler supply outlet pipe.
2. Connect discharge piping to safe disposal location, follow-
ing guidelines in the
7!2.).' below.