Installation & Operating Manual C6501073(0) Single stage operation oil burners RETROFIT APPLICATIONS ONLYIf this burner is being ins
33987GBNPTF - NPT pipe adapterThe BF burner you have purchased is shipped with an NPTFto NPT fitting. This fitting is the connection point for the oil
33988GBPUMP PURGENOTE: To protect the pump gears, it is advisable to lubricate thepump prior to purging a lift system.Apply oil through the VACUUM POR
33989GBCOMBUSTION CHAMBER PRESSURE CHART BURNER OUTPUT VS CHAMBER PRESSURE CHARTD7525(GPH) BURNER OUTPUTCHAMBER PRESSURE(INCHES WC)0.0 0.50 0.75 1.00
339810GBBURNER START-UP CYCLE Normal Lock-out, due to light-failureThermostatMotorIgnition transformerValveFlameLock-out lamp~ 12sec. ~ 12sec
339811GBTROUBLE SHOOTING CHART• Faulty CAD cell or seeing light before trial for ignition.• Coil wire on terminals #1 & 2 or #1 & 8 reversed.•
339812GBA TYPICAL LAYOUT FOR BF BURNER INTAKE AIRA) Use an approved air intake kit.B) Always keep intake air run to the minimum.C) Maximum intake air
133398EXPLODED SPARE PARTS LIST
143398SPARE PARTS LISTNo. CODE DESCRIPTION No. CODE DESCRIPTION1 3008019 • BURNER BACK COVER1 C8111015 • BURNER BACK
339815GBBURNER START- UP FORM *35 Pond Park Rd.Hingham, MA 02043Phone: 781-749-8292Toll Free: 800-992-7637Fax: 781-740-20692165 Meadowpine Blvd.Missis
Technical Support Hotline1-800-4-RIELLO1-800-474-355635 Pond Park RoadHingham, MA 02043Phone 781-749-8292Toll Free 800-992-7637Fax 781-740-2069www.rie
3398GBINSTALLLATION PRECAUTIONSAIR FOR COMBUSTIONDo not install burner in room with insufficient air for combustion. Be sure there is an adequate air
3398GBTABLE OF CONTENTSPACKAGE CONTENTS LIST . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
33981GBPACKAGE CONTENTS LISTYour Riello 40 BF burner should include the following parts. Please check to make sure all parts are present before be-gin
33982GBTECHNICAL DATASPECIFICATIONSBURNER AND MOUNTING FLANGE DIMENSIONSBURNER COMPONENTS IDENTIFICATIONFuel No. 2 Fuel OilBF3 Firing rate - Effective
33983GBMOUNTING THE BURNER TO THE BOILER - Position the MOUNTING GASKET (2) be-tween the flat surface of the UNIVERSALMOUNTING FLANGE (1) installed on
33984GBAPPLICATION FIELD WIRINGOil ValveCapacitorGREENBLUEBLACKBLACKWHITEBLUEMBROWNAL 1009-1Burner Fan-OffTi mer6128N1119327Control B ox530 SE/CYELLOW
33985GBINSTALLATION/REMOVAL OF DRAWER ASSEMBLYRemoval:A) Remove the air pressure switch support(6) from the front shield by the two retain-ing screws
33986GBOIL LINE CONNECTIONSThis burner is shipped with the oil pump set to operate on a single line system. To operate on a two-line system the by-pas